Check whether the inrush current of the motor exceeds the capacity of the generating set. 
Inrush current may be up to 10 times the rated current of the motor. The generating appliance needs to either be able to supply enough VA to meet this requirement, or incorporate a soft-start, or inrush current limiting must be added to the circuit.

If in doubt please call us for advice 01239 623506.